The
EMPIRE Systems Heated Make Up Air Unit is a UL Listed, direct fired
gas burning unit for use in tempering make-up air for installations
requiring frequent air changes. The units conform to ANSI Z83.4
Standards and produce up to 1,000,000 BTU/HR, depending on heating
requirements. Units are designed for natural or propane gas
applications. The heaters are intended for indoor or outdoor
installations in commercial kitchens, factories, foundries and similar
commercial and industrial occupancies where unvented open-flame
combustion equipment is permitted. They are intended to be
installedand used in accordance with the Standards of the National
Fire Protection Association, NFPA No.54 and the National Fuel Gas
Code.
The
unit is UL Listed for discharge in the upflow, downflow or horizontal
positions and in combination with a centrifugal upblast exhaust fan.
Each unit is equipped with controls having the capabilities of stand
alone operation or interfacing with the total integrated system
controls including additional fans, hood light controls and the fire
system. These controls are located either in a UL Listed Control Panel
installed in the ventilation hood's utility cabinet or in a stainless
steel remote panel. Units consist of a galvanized casing with an
elevated gas burner which burns directly in the circulating air
stream. The products of combustion mix with the make-up air which is
introduced into the heater intake directly from outside the building
and the resultant mixture is forced into the building by a centrifugal
type blower. Units are equipped with redundant safety controls. In the
event of flame loss, all gas is shut off to the burner.
Units
are factory assembled, tested and shipped as a complete package,
consisting of the following:
-
Gas burner
-
Centrifugal
blower
-
Motor and
adjustable drive assembly
-
Fuel burning
safety equipment
-
Temperature
control system
-
Gas piping
-
Optional
contactor and overload (for three phase applications)
-
External
service disconnect (with integrated auxiliary contacts for
control circuit, when required)
-
Intake hood
with easily removable 1" thick, UL Listed, cleanable Class
2 filters
-
An
observation port is located on the exterior of the unit to
observe the main flame. The unit is provided with two access
doors for easy access to the Electrical Controls and
Blower/Motor Assembly.
BLOWERS,
MOTORS AND DRIVES
-
Blowers are
forward curved, belt driven, double inlet, centrifugal type and
contain permanently lubricated bearings. Blowers are covered
with an enamel finish. Blower sizes range from 10 inch to 25
inch wheel diameter.
-
Blowers are
factory tested and set at rated speed after installation in the
factory assembled unit. Blower shafts are equipped with keyways.
-
The blower
compartment is completely insulated with UL Listed Class 1
foil-faced fiberglass insulation, 1 inch thick.
-
Motor pulley
is adjustable for balancing CFM's.
-
UL
Recognized motors are open drip proof type with adjustable
drives and motor mount. Adjustable cast iron pulleys and heavy
duty belt(s) are standard.
-
Motor shafts
have keyways.
-
A
Discharge Air Sensor measures discharge air temperature and
sends a signal back to the controller which modulates the gas
flow to achieve desired temperature (not shown).
SPECIFICATIONS:
BURNER

-
The gas
burner is a direct-fired, draw through type, and is sized to
provide the desired output using natural or propane gas at an
inlet supply pressure to the unit of 7" water column
(natural gas) or 11"(propane).
-
The gas
burner provides a maximum temperature rise of 100°F. For
example, outside air of -30°F. can be heated to +70°F. The
flame extends the entire length of the burner at all times when
the system is in operation.
-
The burner
consists of non-clogging, stainless steel combustion baffles
attached to a cast iron gas supply section with no moving parts.
The burner is capable of 100% thermal efficiency with a maximum
turndown ratio of 30 to 1.
-
An
ultraviolet flame detection system is used to prove flame.
-
A Spark
Igniter provides spark to initiate combustion.
WIRING
AND ELECTRICAL
-
The control
circuit voltage is 115 VAC.
-
Wiring in
control enclosures is in accordance with the National Electrical
Code.
-
For 3-phase
applications, an optional starter can be located in the EMPIRE
Systems kitchen ventilation hood utility cabinet or in the
heater unit.
STEPPED
DIRECT IGNITION SYSTEM
-
Employs a
spark ignited proved pilot before allowing full burner
operation. This system conforms to AGA's ANSI Standard Z83.4.
-
High
reliability with fewer gas handling parts (reduces possibility
of leakage).
QUALITY
ASSURANCE
Each
unit is meticulously inspected and tested at the factory for the
following:
-
COMBUSTION
EFFICIENCY (values represent ANSI Z83.4 Standards)
Carbon Monoxide<= 5 ppm maximum average concentration added
to
air stream
Aliphatic Aldehydes <= 1.0 ppm maximum average concentration
added
to air stream
Nitrogen Dioxide <= 0.50 ppm maximum average concentration
added to
air stream
Carbon Dioxide <= 4000 ppm maximum average concentration
added to
air stream
-
CFM AND BTU
VERIFICATION
-
LEAKAGE OF
FUEL HANDLING PARTS
-
OPERATION OF
MOVING PARTS AT RATED SPEED
-
MOTOR INPUT
RATING
-
DIELECTRIC
STRENGTH
-
OPERATION OF
SYSTEM SAFETY CONTROLS
-
RAW MATERIAL
CONFORMANCE TO SPECIFICATION
-
OVERALL
AESTHETICS
-
ALL
OPTIONS INSTALLED AND TESTED
NOTE:
Since field conditions may vary from submitted specifications, the
"Start Up Check List" must be completed to insure proper
operation. Warranty coverage is only validated after the start-up has
been completed