ANSUL R-102

MODEL R-102
(STANDARD UL 300 LISTED)
RESTAURANT FIRE
SUPPRESSION
SYSTEMS
DATA SHEET
FEATURES:
- Low pH Agent
- Proven Design
- Reliable Cartridge Operated
- Aesthetically Appealing
- UL Listed - Meets Requirements of UL 300
APPLICATION :
The Ansul R-102 Restaurant Fire Suppression
System is an automatic, pre- engineered, fire suppression system
designed to protect the following areas associated with cooking
equipment; ventilating equipment including hoods, ducts, plenums, and
filters; fryers; griddles and range tops; upright, natural charcoal, or
chain-type broilers; electric, lava rock, mesquite or gas-radiant
char-broilers and woks.
The system is ideally suitable for use in
restaurants, hospitals, nursing homes, hotels, schools, airports, and
other similar facilities.
Use of the R-102 system is limited to interior
applications only. The regulated release and tank assemblies must be
mounted in an area where the air temperature will not fall below 32F
(0C) or exceed 130F (54C). The system must be designed and installed
within the guidelines of the UL Listed Design, Installation, Recharge,
and Maintenance Manual.
SYSTEM DESCRIPTION :
The restaurant fire suppression system is a
pre-engineered, wet chemical, cartridge- operated, regulated pressure
type with a fixed nozzle agent distribution network. It is listed with
Underwriters Laboratories, Inc. (UL).
The system is capable of automatic detection
and actuation and/or remote manual actuation. Additional equipment is
available for mechanical or electrical gas line shut-off applications.
The detection portion of the fire suppression
system allows for automatic detection by means of specific alloy rated
fusible links, which, when the temperature exceeds the rating of the
link, the link separates, allowing the regulated release to actuate.
A system owner's guide is available containing
basic information pertaining to system operation and maintenance. A
detailed technical manual is also available including system
description, design, installation, recharge, and maintenance procedures,
plus additional equipment installation and resetting instructions.
The system is installed and serviced by
authorized distributors that are trained by the manufacturer.
The basic system consists of an ANSUL AUTOMAN
regulated release assembly which includes a regulated release mechanism
and a wet chemical storage tank housed within a single enclosure. Nozzle
blow-off caps, detectors, cartridges, agent, fusible links, and pulley
elbows are supplied in separate packages in the quantities need- ed for
fire suppression system arrangements.
Additional equipment includes remote manual
pull station, mechanical and electrical gas valves, pressure switches,
and electrical switches for automatic equipment and gas line shut-off.
Accessories can be added such as alarms, warning lights, etc., to
installations where required.
Tanks can be used in multiple arrangements to
allow for larger hazard coverage. Each tank is limited to a listed
maximum amount of flow numbers.
COMPONENT DESCRIPTION:
- Wet Chemical Agent
- The extinguishing agent is a potassium carbonate, potassium
acetate-based formulation designed for rapid flame knockdown and
foam securement of grease related fires. It is available in plastic
containers with instructions for wet chemical handling and usage.
- Agent Tank -
The agent tank is installed in a stainless steel enclosure or wall
bracket. The tank is deep drawn carbon steel finished in red enamel.
Tanks are available in two sizes: 1.5 gallon (5.7 L) and 3.0 gallon
(11.4 L). The tanks have a working pressure of 100 psi (6.9 bar), a
test pressure of 300 psi (20.7 bar), and a minimum burst pressure of
600 psi (41.4 bar). The tank includes an adaptor/tube assembly. The
adaptor is chrome-plated steel with a 1/4 in. NPT female gas inlet
and a 3/8 in. NPT female agent outlet. The adaptor also contains a
bursting disc seal which prevents the siphoning of agent up the pipe
during extreme temperature variations.
- Regulated Release
Mechanism - The regulated release mechanism is a
spring-loaded, mechanical/pneumatic type capable of providing the
expellant gas supply to one or two agent tanks, depending on the
capacity of the gas cartridge used. It contains a factory installed
regulator deadset at 100 psi (6.9 bar) with an internal relief of
approximately 145 psi (10.0 bar). It has automatic actuation
capabilities by a fusible link detection system and remote manual
actuation by a mechanical pull station. The regulated release
mechanism contains a release assembly, regulator, expellant gas
hose, and agent storage tank housed in a stainless steel enclosure
with cover. The enclosure contains knock-outs for 1/2 in. conduit.
The cover contains an opening for a visual status indicator. It is
compatible with mechanical gas shut-off devices; or, when equipped
with a field or factory-installed switch, it is compatible with
electric gas line or appliance shut-off devices.
- Regulated Actuator
Assembly - When more than two agent tanks are required, the
regulated actuator is available to provide expellant gas for
additional tanks. It is connected to the cartridge receiver outlet
of the regulated release mechanism providing simultaneous agent
discharge. It contains a regulated actuator deadset at 100 psi (6.9
bar) with an internal relief of approximately 145 psi (10.0 bar).The
regulated actuator assembly contains a regulated actuator,
regulator, expellant gas hose, and agent tank housed in a stainless
steel enclosure with cover. The enclosure contains knockouts to
permit installation of the expellant gas line.
- Discharge Nozzles
- Each discharge nozzle is tested and listed with the R-102 system
for a specific application. Nozzle tips are stamped with the flow
number designation (1/2, 1, 2, and 3). Each nozzle must have a metal
or rubber blow-off cap to keep the nozzle tip orifice free of
cooking grease build-up.
APPROVALS :
Applicable Standards:
ULI listed under EX- 3470; ULC listed under CEX-747; meets requirements
of NFPA 96 (Standard for the Installation of Equipment for the Removal
of Smoke and Grease-Laden Vapors from Commercial Cooking Equipment);
NFPA 17A (Standard on Wet Chemical Extinguishing Systems).
ORDERING INFORMATION
Order all system components through your local
authorized Ansul Distributor.
SPECIFICATIONS:
An Ansul R-102 Fire Suppression System shall
be furnished. The system shall be capable of protecting all hazard areas
associated with cooking equipment.
GENERAL:
References:
Submittals:
- Submit two sets of manufacturer's data
sheets
- Submit two sets of piping design drawings
System Description:
The system shall be an automatic fire
suppression system using a wet chemical agent for grease related
fires.The system shall be capable of suppressing fires in the following
areasassociated with cooking equipment: ventilating equipment including
hoods, ducts, plenums, and filters; fryers; griddles and range tops;
upright, natural charcoal, or chain-type broilers; electric, lava rock,
mesquite or gas-radiant char-broilers.The system shall be the
pre-engineered type having minimum and maximum guidelines established by
the manufacturer and listed by Underwriters Laboratories, Inc. (UL).The
system shall be installed and serviced by personnel trained by the
manufacturer.
Quality Control:
Manufacturer: The
R-102 Restaurant Fire Suppression System shall be manufactured by a
company with at least thirty years experience in the design and
manufacture of pre-engineered fire suppression systems. The manufacturer
shall be ISO 9002 registered.
Certificates: The
wet agent shall be a specially formulated, aqueous solution of organic
salts with a pH range between 7.8 - 8.2, designed for flame knockdown
and foam securement of grease-related fires.
Warranty, Disclaimer, and
Limitations:
The pre-engineered restaurant fire suppression
system components shall be warranted for five years from date of
delivery against defects in workmanship and material.
Delivery:
Packaging: All
system components shall be securely packaged to provide protection
during shipment.
Environmental Conditions:
The R-102 system shall be capable of operating
in a temperature range of 32F to 130F (0C to 54C).
PRODUCT:
- Manufacturer:
Ansul Fire Protection
One Stanton Street
Marinette, Wisconsin 54143-2542
Telephone (715) 735-7411.
- Components:The
basic system shall consist of an ANSUL AUTOMAN regulated release
assembly which includes a regulated release mechanism and a wet
chemical storage tank housed within a single enclosure. Nozzles,
blow-off caps, detectors, cartridges, agent, fusible links, and
pulley elbows shall be supplied in separate packages in the
quantities needed for fire suppression system arrangements.
Additional equipment shall include remote manual pull station,
mechanical and electrical gas valves, pressure switches, and
electrical switches for automatic equipment and gas line shut-off.
- Wet Chemical Agent:
The extinguishing agent shall be a specially formulated, aqueous
solution of organic salts with a pH range between 7.8 - 8.2,
designed for flame knockdown and foam securement of grease related
fires.
- Agent Tank:
The agent tank shall be installed in a stainless steel enclosure or
wall bracket. The tank shall be deep drawn carbon steel finished in
red enamel. Tanks shall be available in two sizes; 1.5 gallon (5.7
L) and 3.0 gallon (11.4 L).The tanks shall have a working pressure
of 100 psi (6.9 bar), a test pressure of 300 psi (20.7 bar), and a
minimum burst pressure of 600 psi (41.4 bar). The tank shall include
an adaptor/tube assembly containing a burst disc union.
- Regulated Release
Mechanism: The regulated release mechanism shall be a
spring-loaded, mechanical/pneumatic type capable of providing the
expellant gas supply to one or two agent tanks depending on the
capacity of the gas cartridge used. It shall contain a factory
installed regulator deadset at 100 psi (6.9 bar) with an internal
relief of approximately 145 psi (10.0 bar). It shall have the
following actuation capabilities: automatic actuation by a fusible
link detection system and remote manual actuation by a mechanical
pull station. The regulated release mechanism shall contain a
release assembly, regulator, expellant gas hose, and agent storage
tank housed in a stainless steel enclosure with cover. The enclosure
shall contain knock-outs for 1/2 in. conduit. The cover shall
contain an opening for a visual status indicator.It shall be
compatible with mechanical gas shut-off devices; or, when equipped
with a field or factory-installed switch, it shall be compatible
with electric gas line or appliance shut-off devices.
- Regulated Actuator
Assembly: When more than two agent tanks are required, the
regulated actuator shall be available to provide expellant gas for
additional tanks. It shall be connected to the cartridge receiver
outlet of the regulated release mechanism providing simultaneous
agent discharge. The regulator shall be deadset at 100 psi (6.9 bar)
with an internal relief of approximately 145 psi (10.0 bar). The
regulated actuator assembly shall contain a regulated actuator,
regulator, expellant gas hose, and agent tank housed in a stainless
steel enclosure with cover. The enclosure shall contain knockouts to
permit installation of the expellant gas line.
- Discharge Nozzles:
Each discharge nozzle shall be tested and listed with the R-102
system for a specific application. Nozzles tips shall be stamped
with the flow number designation (1/2, 1, 2, and 3). Each nozzle
shall have a metal or rubber blow-off cap to keep the nozzle tip
orifice free of cooking grease build-up.
- Distribution Piping:
Distribution piping shall be Schedule 40 black iron, chrome-plated,
or stainless steel pipe conforming to ASTM A120, A53, or A106.
- Detectors: The
detectors shall be the fusible link style designed to separate at a
specific temperature.
- Cartridges:
The cartridge shall be a sealed steel pressure vessel containing
either carbon dioxide or nitrogen gas. The cartridge seal shall be
designed to be punctured by the releasing device supplying the
required pressure to expel wet chemical agent from the storage tank.
IMPLEMENTATION:
- Installation:The
R-102 fire suppression system shall be designed, installed,
inspected, maintained, and recharged in accordance with the
manufacturer's listed instruction manual.
- Training:Training
shall be conducted by representatives of the manufacturer.
ANSUL FIRE PROTECTION
MARINETTE, WI 54143-2542
715-735-7411
|